
PRT-ISO16-DIN
The Protege DIN Rail 16 Input Opto-Isolated Expander provides the interface of up to 16 low or high voltage signals to the Protege integrated access control, security and building automation system, an advanced technology security product providing seamless and powerful integration.
Special Features
- 16 opto-isolated inputs capable of handling high voltage DC and AC signals
- Connect any combination of normally closed or normally open inputs
- Utilizes analog to digital processing with 5 times over sampling
- 2 state zone alarm providing alarm and closed conditions
- 4 50mA (Max) open collector outputs
- High Performance 32 Bit processor
- Designed for use with industry standard DIN Rail mounting
Technical Specifications
| DC Input Voltage | 11-14V DC |
| DC Output Voltage (DC IN Pass-Through) | 10.45-13.85VDC 0.7A (Typical) Electronic Shutdown at 1.1A |
| Operating Current | 80mA (typical) |
| Low Voltage Cutout | 8.7VDC |
| Low Voltage Restore | 10.5VDC |
| RS-485 | Isolated module network |
| Operating Voltage | 10V to 250V (DC/AC RMS) 35-75Hz |
| Input Type | 16 galvanic isolated (10ms to 1hr input speed programmable) |
| Input Current Drawn | Current 2mA per input at 220VDC |
| Outputs | 2 50mA (max) open collector |
| Dimensions (L x W x H) | 156.8 x 90 x 60mm (6.17 x 3.54 x 2.36″) |
| Weight | 289g (10.2oz) |
| Operating | -10° to 55°C (14° to 131°F) |
| Storage | -10°- 85°C (14° – 185°F) |
| Humidity | 0%-93% non condensing, indoor use only (relative humidity) |
| Mean Time Between Failures (MTBF) | 784,316 hours (calculated using RFD 2000 (UTE C 80-810) Standard) |
Other Features
Power Supply
The Protege DIN Rail 16 Input Opto-Isolated Expander operates from a 12VDC input. Ultra low current requirements ensure cost effective power distribution.
Connectivity and System Expansion
Expanding the Protege System with local inputs and outputs from the Protege DIN Rail 16 Input Opto-Isolated Expander allows convenient cost effective expansion and added benefit of:
> 16 opto-isolated inputs capable of a large voltage range, ideal for use in lift control or automation installs
> 4 multiple function outputs for use in any programmable output entry, ideal for connection in an electrical switch room to control signage, lighting and building automation or system indicators
> Address configuration is achieved using the address programming feature of the Protege System Controller
Communication
Single RS-485 communication interface port used for all network communication functions and interconnects to other modules.
Upgradable Firmware
Utilizing the latest flash technology and high performance communication mediums, the firmware of the Protege DIN Rail 16 Input Opto-Isolated Expander can be updated using the ICT Loadit utility over the Protege system module network.
